Zhejiang, China
Business Type:
Group Corporation
Number of Employees:
366
Year of Establishment:
1996-04-03
Management System Certification:
ISO9001:2008, ISO14001:2004, OHSAS18001:2007
OEM/ODM Availability:
Yes
OEM/ODM Service
Sample Available
MEI Awards

RCCB, Residual Current Circuit Breakers, RCD manufacturer / supplier in China, offering Residual Current Circuit Breakers Household RCCB, MCB with Shunt Release 6ka Rdx12-63s 3p+N, MCB with Overvoltage Undervoltage Protection Rdx16-63gq 1p+N and so on.

Gold Member Since 2005
Audited Supplier
Supplier Homepage Products Circuit Breaker MCB Residual Current Circuit Breakers Household RCCB
  • Residual Current Circuit Breakers Household RCCB
  • Residual Current Circuit Breakers Household RCCB

Residual Current Circuit Breakers Household RCCB

Get Latest Price
Min. Order / Reference FOB Price
10 Pieces US $4.5/ Piece
Port: Ningbo, China
Production Capacity: 800, 000 PCS/Per Month
Payment Terms: L/C, T/T, Western Union
Breaking Capacity: Low Voltage Circuit Breakers
Operation: Manual Type
Speed: High-Speed Circuit Breaker
Arc-extinguishing Medium: Air
Installation: DIN Rail
Structure: Moulded Case Circuit Breaker

You Might Also Like

Loading...

Basic Info

Model NO.: PID-63/RDL67
Type: Circuit Breaker
Function: Overcurrent Protection
Certification: CE, CCC
Brand Name: People
Model: Residual Current
Color: White
Rated Current: 16, 20, 25, 40, 50, 63A
Rated Residual Current: 30, 100, 300, 500mA
Trademark: PEOPLE
Transport Package: Carton
Specification: CCC, CE, CB
Origin: Wenzhou, Zhejiang
HS Code: 85362000

Product Description

Introduction
PID-63 can be used to cut off the fault circuit on the occasion of shock hazard or earth leakage of trunk line, It conforms to IEC61008.

Key Specifications/Special Features:
Rated voltage (Un): 230 and 400V
Rated current: 16, 25, 32, 40 and 63A
Rated frequency: 50/60Hz
Rated breaking capacity: 6kA
Energy limiting class: 3
Rated fault current: 10, 30, 100, 300 and 500mA
Cross-section of connecting lead 1 to 25mm
Isolating class B
Mounting on rail EN 60715 (EN 50022)
Pole numbers: 2 and 4p
Type: A and AC
Standards: IEC61008, EN61008 and VDE0664
Certifications: CE and SAA
TypePID-63
Number of pole1P+N, 3P+N
Rated current(A)16, 20, 25, 40, 50, 63
Rated residual operating current In(mA)30, 100, 300, 500
Rated voltage(V)AC230/240, AC400/415
Residual operating current scope0.5 In~1In
Residual current off-time≤ 0.3S
Short circuit capacity Icu6000A
Endurance4000
Protection degreeIP20