  • Model NO.: RDX2-125S
  • Operation: Manual Type
  • Arc-extinguishing Medium: Air
  • Structure: MCB
  • Type: Circuit Breaker
  • Certification: ISO9001-2000, CCC
  • Rated Current: 40~125A
  • Materials: Fire-Resistance ABS, Sliver, Copper, Steel
  • Specification: CCC, CE
  • HS Code: 85362000
  • Breaking Capacity: Low Voltage Circuit Breakers
  • Speed: Normal Type Circuit Breaker
  • Installation: DIN Rail
  • Poles Number: 1p, 2p, 3p, 4p
  • Function: Overcurrent Protection
  • Brand Name: People
  • Braeking Capacity: 6ka
  • Trademark: PEOPLE
  • Origin: Wenzhou, Zhejiang
Product Description
Application
RDX2-125S high breaking capacity shunt release miniature circuit breaker. The product is suitable for the control circuit, AC50/60Hz, rated working voltage 230/400V, rated current 125A. Can remotely control break & automatic signal control break, as well with overload & shortcircuit protection for circuit. Unfrequent switching operation under normal conditions. Widely used in single-phase/three phases smart prepaid power meter(IC card), to realize close& open of control circuit. 
It complies with IEC60898-1standard.

Normal working & installment conditions
1.Ambient temperature: -5ºC~+40ºC, 24 hours average temperature not exceed +35ºC.
2.Installment plance altitude: ≤2000m
3.Gas relative humidity:not exceed 50% at +40ºC, higher humidity allowed at lower temperature.
4.Pollution degree: 2 class
5.Installment condition: Mounted in the place without obvious impact or shock, no dangerous(explosion) dielectric without corrosive metal or damaging isolation gas(conductive dust).
6.Installment method: TH35-7.5 mounted rail, can be installed in distribution board, case or box. Generally mounted vertically. Tilted angle between mounting face and vertical face not exceed ±5°.
7.Mounted Category: II,III class.

Specification
1.Shortcircuit tripping feature: C type 5~10In; D type 10~14In
2.Rated control power source voltage Us: 230V
Rated voltage230/400V
Rated current 63, 80, 100,125A
Case class125A
Breaking capacity6KA 
Signal control tripper action time0.5s ≤t<3s
Width pole54mm
According to standandsIEC60898, GB10963.1

Overcurrent delay acting feature
NoSetting current time(h)Estimated resultStart
In≤63AIn>63A
11.13In≤1≤2No tripCold
21.45In<1<2TripHot
35(10)InT≤0.1sNo tripCold
410(14)InT<0.1sTripCold